How to Perform Step Introduction in RG3 Series Power factor controllers?
At the end of the operations that are affecting compensation such as capacitor change, the automatic step identification (Auto Setup) operation must be performed over the power factor controller. The following steps should be followed for this process;
- Initially, enter the menu by pressing and holding the "setting" button for 3 seconds.
- “Auto” appears on the screen. By pressing the "set" button again, the "auto operator???" menu is entered.
- Press the up arrow button once to go to the “auto setup”, press the “Set” button and then “off” option is made “on” with the up arrow button.
- By pressing the "set" button again, automatic recognition and operation are started.